9kW R290 Monobloc Air to water Heat Pump & Control Unit, 3 Phase, with low GWP & Quiet Operation, 75°C Max Heating

9kW R290 Monobloc Air to water Heat Pump & Control Unit, 3 Phase, with low GWP & Quiet Operation, 75°C Max Heating

All Spec

POWER SUPPLY

  • Voltage, phase, frequency for indoor unit (V, Ø, Hz)

    220 ~ 240, 1, 50

  • Voltage, phase, frequency for outdoor unit (V, Ø, Hz)

    380 ~ 415, 3, 50

DIMENSIONS

  • Indoor unit (W × H × D) (mm)

    420 x 490 x 141

  • Outdoor unit (W × H × D) (mm)

    1,560 x 1,019 x 520

WEIGHT

  • Indoor unit (Empty) (kg)

    6.7

  • Outdoor unit (Empty) (kg)

    181.0

EXTERIOR

  • Color of outdoor unit chassis (Color / RAL code)

    Dawn gray / RAL 7037

  • Color of outdoor unit front grille (Color / RAL code)

    Dark dawn gray / RAL 7012

  • Indoor unit (Color / RAL code)

    Essence White / RAL 9003

REFRIGERANT

  • Type

    R290

  • GWP

    3

  • Precharged amount (g)

    1,200

SOUND POWER LEVEL (OUTDOOR UNIT)

  • Rated / low noise mode (dB(A))

    49 / 48

NOMINAL CAPACITY AND COP (A-7/W+35)

  • COP

    3.44

  • Heating capacity (kW)

    8.90

NOMINAL CAPACITY AND COP (A-7/W+55)

  • COP

    2.43

  • Heating capacity (kW)

    7.00

NOMINAL CAPACITY AND COP (A+2/W+35)

  • COP

    3.88

  • Heating capacity (kW)

    9.00

NOMINAL CAPACITY AND COP (A+7/W+35)

  • COP

    4.90

  • Heating capacity (kW)

    9.00

NOMINAL CAPACITY AND COP (A+7/W+55)

  • COP

    3.20

  • Heating capacity (kW)

    9.00

NOMINAL CAPACITY AND EER (A+35/W+18)

  • Cooling capacity (kW)

    9.00

  • EER

    3.90

NOMINAL CAPACITY AND EER (A+35/W+7)

  • Cooling capacity (kW)

    9.00

  • EER

    3.24

OPERATION RANGE (LEAVING WATER TEMPERATURE)

  • Cooling (Min. ~ Max.) (℃)

    5 ~ 27

  • DHW (Min. ~ Max.) (℃)

    15 ~ 80

  • Heating (Min. ~ Max.) (℃)

    15 ~ 75

OPERATION RANGE (OUTDOOR AIR TEMPERATURE)

  • Cooling (Min. ~ Max.) (℃)

    5 ~ 48

  • Heating & DHW (Min. ~ Max.) (℃)

    -28 ~ 35

PIPING CONNECTIONS (WATER/OUTDOOR UNIT)

  • Inlet diameter (inch)

    Male PT 1"

  • Outlet diameter (inch)

    Male PT 1"

SEASONAL EFFICIENCY DATA (HEATING)

  • SCOP (35℃ / 55℃)

    5.23 / 3.75

  • Seasonal space heating efficiency (ηS) (35℃ / 55℃)

    206 / 147

  • Seasonal space heating eff. class (35℃ / 55℃)

    A+++/A++

SOUND PRESSURE LEVEL AT 5M (OUTDOOR UNIT, CONVERT USING SWL)

  • Rated / low noise mode (dB(A))

    27 / 26

COMPLIANCE INFORMATION

The safety information for accessories is included with the safety information for the product and is not provided separately.
To learn more about how this product handles data and your rights as a user, please visit ″Data Coverage & Specifications″ at LG Privacy