AB-Q36GM3T2
Inverter Ducted Dx 2.8 TR, Inverter Compressor, Corrosion resistant heat exchanger, Quick Cooling
Inverter Ducted Dx 2.8 TR, Inverter Compressor, Corrosion resistant heat exchanger, Quick Cooling
MSRP AED

INDOOR SPECIFICATIONS

  • Capacity Cooling (Min.∼Rated∼Max.) - ㎾
    4.70 ~ 9.95 ~ 11.13
    Capacity Cooling (Min.∼Rated∼Max.) - Btu/h
    16,030 ~ 34,000 ~ 38,000
  • Power Input Cooling (Rated) - ㎾
    2.85
    Running Current Cooling (Rated/Max) - A
    12.9 / 17.0
  • Efficiency EER (T1) - Btu/h W
    11.95
    Efficiency EER (T3) - Btu/h W
    9.30
  • Power Supply - V, Ø, ㎐
    230, 1, 50
    Power Factor Cooling (Rated)
    0.99
  • Casing Color
    Warm Gray
    Dimensions Net (W × H × D) - ㎜
    1,250 × 360 × 700
  • Dimensions Shipping (W × H × D) - ㎜
    1,450 × 428 × 773
    Weight Net - ㎏
    37.5
  • Weight Shipping - ㎏
    45.0
    Heat Exchanger (Rows × Columns × FPI) × No.
    (3 × 16 × 18) × 1
  • Heat Exchanger Face Area - ㎡ (ft²)
    0.36 (3.87)
    Fan Type
    Sirocco
  • Fan Air Flow Rate (H / M / L) - ㎥/min
    32.0 / 28.0 / 24.0
    Fan Air Flow Rate (External Static Pressure-Factory Set) - ㎜Aq
    8
  • Fan Motor Type
    BLDC
    Fan Motor Output - W × No.
    154 × 1
  • Fan Motor FLA (Full Load Ampere) - A
    1.90
    Dehumidification Rate - ℓ/h
    1.9
  • Sound Pressure Level (H / M / L) - dB(A)
    36 / 33 / 31
    Piping Connections Liquid Side - ㎜(inch)
    Ø 9.52 (3/8)
  • Piping Connections Gas Side - ㎜(inch)
    Ø 15.88 (5/8)
    Piping Connections Drain Pipe (O.D. / I.D.) - ㎜
    Ø 32.0 / 25.0
  • Safety Devices
    Fuse
    Refrigerant Control
    Electronic Expansion Valve
  • Power and Communication Cable (included Earth) - No. × ㎟
    4C × 0.75

OUTDOOR SPECIFICATIONS

  • Capacity Cooling (Min.∼Rated∼Max.) - ㎾
    4.70 ~ 9.95 ~ 11.13
    Capacity Cooling (Min.∼Rated∼Max.) - Btu/h
    16,030 ~ 34,000 ~ 38,000
  • Power Input Cooling (Rated) - ㎾
    2.85
    Running Current Cooling (Rated/Max) - A
    12.9 / 17.0
  • Efficiency EER (T1) - Btu/h W
    11.95
    Efficiency EER (T3) - Btu/h W
    9.30
  • Power Supply - V, Ø, ㎐
    230, 1, 50
    Casing Color
    Warm Gray
  • Dimensions Net (W × H × D) - ㎜
    950 × 834 × 330
    Dimensions Shipping (W × H × D) - ㎜
    1,065 × 918 × 461
  • Weight Net - ㎏
    60.0
    Weight Shipping - ㎏
    67.5
  • Heat Exchanger (Rows × Columns × FPI) × No.
    (2 × 38 × 14) × 1
    Compressor Type
    Twin Rotary
  • Compressor Model / Compressor Model - Model × No.
    GJT325MAA × 1
    Compressor Motor type
    BLDC
  • Compressor Motor Output - W × No.
    2,137 × 1
    Fan Type
    Axial Fan
  • Fan Air Flow Rate - ㎥/min × No.
    70 × 1
    Fan Motor Type
    BLDC
  • Fan Motor Output - W × No.
    124.2 × 1
    Sound Pressure Level Cooling (Rated) - dB(A)
    51
  • Piping Connections Liquid Side (Outer Dia.) - ㎜(inch)
    Ø 9.52 (3/8)
    Piping Connections Gas Side (Outer Dia.) - ㎜(inch)
    Ø 15.88 (5/8)
  • Piping Length (Min./Max.) - m
    5 / 50
    Refrigerant Type
    R410A
  • Refrigerant Precharged Amount - g
    2,200
    Refrigerant GWP(Global Warming Potential)
    2,087.5
  • Refrigerant tCO2-eq
    4.593
    Refrigerant Chargeless-Pipe Length - m(ft)
    7.5 (24.6)
  • Refrigerant Additional Charging Volume - g/m(oz/ft)
    40 (0.43)
    Refrigerant Control
    Electronic Expansion Valve
  • Refrigerant Oil Type
    FVC68D
    Refrigerant Oil Charged volume - cc × No.
    950 × 1
  • Wiring Connections Power Supply Cable (included Earth) - No. × ㎟
    3C × 2.5
    Maximum Height Difference Outdoor Unit ~ Indoor Unit (Max.) - m(ft)
    30 (98.4)

To access more technical documentation and downloads, please visit the LG B2B Partner Portal.

Find a dealer to help with service for sales, installation, and after sales.
Country is required
Address Unit is required.
Business Unit is required
  • sales
  • install
  • service
Please retry to enter zip code.

There is no data. Please retry to enter zip code.

Compare

0