Causes and Symptoms
- The power cord is loosely plugged in.
- A power strip is being used.
- It is necessary to check the remote control of the air conditioner.
Air conditioners are electrical appliances that consume a lot of power.
Use an exclusive circuit breaker for the air conditioner and connect the product to a dedicated wall
outlet.
If a power strip must be used due to the installation environment, use a 16 or higher amps power strip with
a cable thickness between 2~2.5mm. (0.07~0.1 in) The air conditioner must be used alone.
Try this
If the power cord is loosely plugged in, the power cord may overheat or the power may be turned off.
➔ Unplug the power cord, and cool heat for approximately 30 minutes. Then, correctly plug the code in to start the product again.
If your product is a model with the hidden power cord, check the dedicated circuit breaker for the air conditioner.
The dedicated circuit breaker for an air conditioner is adjacent to the shoe chest on the front door of your
house, and the circuit breaker is marked with Air Conditioner, or A/C.
Trip the circuit breaker, and then reset it.
It is preferable that a power strip is not used and that the air conditioner is connected to an exclusive power outlet on the wall.
If a power strip must be used due to the installation environment, use a 16 or higher amps power strip with a cable thickness between 2~2.5mm(0.07~0.1 in). The air conditioner must be used alone.
A multi strip cannot be used for stand type air conditioners.
There is a risk of fire even if it is used alone due to the maximum current drawn by the single stand
type air conditioner.
How to check capacity of power strip
Optimum capacity: 80% of maximum capacity or lower [16A x 250V x 0.8 = 3200W or lower]
The recommended maximum current of air conditioner of capacity is between 16A and 20A depending on floor size when using power strip. Power may be turned off when plugging other electric apparatus in the same power strip, or outdoor unit overheats due to intense heat.