9kW R290 Monobloc Air to water Heat Pump & Control Unit, 3 Phase, with low GWP & Quiet Operation, 75°C Max Heating

9kW R290 Monobloc Air to water Heat Pump & Control Unit, 3 Phase, with low GWP & Quiet Operation, 75°C Max Heating

*All tests were conducted according to LG's internal test policy and environment.

*Product’s lifecycle might vary depends on actual usage environment.

*LG BECON cloud service availability can be varied by each country.

Key Feature

  • • Natural refrigerant R290 with low GWP (3)
  • • No refrigerant piping work
  • • ErP energy label class LWT A+++/A+++ (35°C/55°C)
  • • Refined gray design that adapts to various surroundings
  • • High leaving water temperature up to 75°C and wide operating range down to -28°C ambient temperature
  • • One of the quietest models on the market (49 dB(A) for 12 kW models)

All Spec

POWER SUPPLY

  • Voltage, phase, frequency for indoor unit (V, Ø, Hz)

    220 ~ 240, 1, 50

  • Voltage, phase, frequency for outdoor unit (V, Ø, Hz)

    380 ~ 415, 3, 50

DIMENSION

  • Indoor unit (W × H × D) (mm)

    420 x 490 x 141

  • Outdoor unit (W × H × D) (mm)

    1,560 x 1,019 x 520

WEIGHT

  • Indoor unit (Empty) (kg)

    6.7

  • Outdoor unit (Empty) (kg)

    181.0

EXTERIOR

  • Color of outdoor unit chassis (Color / RAL code)

    Dawn gray / RAL 7037

  • Color of outdoor unit front grille (Color / RAL code)

    Dark dawn gray / RAL 7012

  • Indoor unit (Color / RAL code)

    Essence White / RAL 9003

REFRIGERANT

  • Type

    R290

  • GWP

    3

  • Precharged amount (g)

    1,200

SOUND POWER LEVEL (OUTDOOR UNIT)

  • Rated / low noise mode (dB(A))

    49 / 48

NOMINAL CAPACITY AND COP (A-7/W+35)

  • COP

    3.44

  • Heating capacity (kW)

    8.90

NOMINAL CAPACITY AND COP (A-7/W+55)

  • COP

    2.43

  • Heating capacity (kW)

    7.00

NOMINAL CAPACITY AND COP (A+2/W+35)

  • COP

    3.88

  • Heating capacity (kW)

    9.00

NOMINAL CAPACITY AND COP (A+7/W+35)

  • COP

    4.90

  • Heating capacity (kW)

    9.00

NOMINAL CAPACITY AND COP (A+7/W+55)

  • COP

    3.20

  • Heating capacity (kW)

    9.00

NOMINAL CAPACITY AND EER (A+35/W+18)

  • Cooling capacity (kW)

    9.00

  • EER

    3.90

NOMINAL CAPACITY AND EER (A+35/W+7)

  • Cooling capacity (kW)

    9.00

  • EER

    3.24

OPERATION RANGE (LEAVING WATER TEMPERATURE)

  • Cooling (Min. ~ Max.) (℃)

    5 ~ 27

  • DHW (Min. ~ Max.) (℃)

    15 ~ 80

  • Heating (Min. ~ Max.) (℃)

    15 ~ 75

OPERATION RANGE (OUTDOOR AIR TEMPERATURE)

  • Cooling (Min. ~ Max.) (℃)

    5 ~ 48

  • Heating & DHW (Min. ~ Max.) (℃)

    -28 ~ 35

PIPING CONNECTIONS (WATER/OUTDOOR UNIT)

  • Inlet diameter (inch)

    Male PT 1"

  • Outlet diameter (inch)

    Male PT 1"

SEASONAL EFFICIENCY DATA (HEATING)

  • SCOP (35℃ / 55℃)

    5.23 / 3.75

  • Seasonal space heating efficiency (ηS) (35℃ / 55℃)

    206 / 147

  • Seasonal space heating eff. class (35℃ / 55℃)

    A+++/A++

SOUND PRESSURE LEVEL AT 5M (OUTDOOR UNIT, CONVERT USING SWL)

  • Rated / low noise mode (dB(A))

    27 / 26

COMPLIANCE INFORMATION

The safety information for accessories is included with the safety information for the product and is not provided separately.
To learn more about how this product handles data and your rights as a user, please visit ″Data Coverage & Specifications″ at LG Privacy

To access more technical documentation and downloads, please visit the LG B2B Partner Portal.